Skip to content
Skip to content
Welcome to Perfect Pollucon Services Office Hours: 10:00am-7:00pm
Perfect Pollucon Services

Perfect Pollucon Services

Environmental Consultant & Laboratory

Call Us 9967436537
Mail Us [email protected]
Maharashtra, India 3 Krishna Koyna B, Majiwada, Thane W
  • Home
  • Monitoring Services
    • Ambient Air Quality Monitoring & Testing
    • Indoor Air Quality Monitoring & Testing
    • Air Quality Monitoring & Testing
    • Stack Emission Monitoring & Testing
    • Noise Level Monitoring & Testing
    • Food Testing Laboratory Services
    • Fugitive Emission Monitoring & Testing
    • Soil Testing & Investigation Laboratory
    • Drinking Water Quality Testing & Analysis Laboratory
    • Corrosion Testing Services
    • Illumination Survey / Lux Monitoring
    • Ventilation Survey
  • Consultancy Services
    • Environmental Impact Assessment
    • Environmental Statement Form V
    • MPCB Consent to Establish, Operate and Renewal
    • Operation and maintenance of Effluent Treatment Plant
    • Effluent Treatment Plant Design
    • Water Cess returns
    • Self Audit Report MPCB
  • Industries
    • Pharmaceutical Industries
    • Chemical and Petrochemical Industry
    • Construction & Real Estate
    • Oil and Gas Or Petroleum Industry
    • Manufacturing / Production Industry
    • Corrosion Control at Data Center / IT Industry
    • Mining and Mineral Extraction
    • Food & Cold Storage Industry
    • Supply Chain & Warehouses
    • Data Centres
    • Railways & Metro Projects
    • Hospitality & Tourism
    • Retail and Shopping Malls
  • Blog
  • Tools
    • Air Monitoring Calculators
    • Stack Monitoring Calculators
    • Noise Monitoring Calculators
    • Lux & Illuminance Calculators
    • Carbon & Energy Footprint Calculators
    • ETP & STP Calculators for Form-V
    • ETP Design Calculators
  • About Us
    • Our Work and Clients
    • Case Studies
    • Testimonials & Leave Us a Review
    • Trusted Partners
    • Careers
    • Guest Posting – Write for Us
    • Press Release
    • Our Features
      • Locally Recognized
      • Affordable Pricing
      • Priority Service
  • Contact Us
REQUEST A QUOTE
DG Insertion Loss Testing for DG Sets – CPCB Noise Compliance
Perfect Pollucon Services

DG Insertion Loss Testing for DG Sets – CPCB Noise Compliance

Diesel generator sets can become major sources of industrial noise. DG Insertion Loss is a critical acoustic metric used to evaluate the effectiveness of silencers and enclosures in reducing generator noise. At Perfect Pollucon Services, we help industries across India achieve compliance through accurate insertion loss testing—ensuring they meet CPCB noise norms without risking closure or penalties.

Diesel generators (DGs) are widely used as backup power sources in industries, commercial spaces, and even residential areas. While essential for energy security, these generators are known for their noise emissions, which can disturb surrounding environments and contribute to noise pollution. One crucial way to control this noise is by reducing the insertion loss of the exhaust muffler of a diesel generator set. In this context, the term “insertion loss” refers to the reduction in noise that occurs when a muffler or acoustic enclosure is installed.

The minimum required DG insertion loss sets is 25 decibels (dB(A)), a standard that applies to all DGs with a rated capacity of up to 1000 kilovolt-amperes (kVA) in India. In this article, we’ll explore what DG insertion loss means, its importance, and additional guidelines for the use of DG sets, including acoustic enclosures, noise control, installation, maintenance, and certification requirements.

1. What is DG Insertion Loss?

DG Insertion loss refers to the reduction in sound level as it passes through a sound barrier or muffler. For diesel generators, this sound barrier is typically an exhaust muffler or an acoustic enclosure. The insertion loss of a DG set’s muffler is the difference between the sound levels before and after the muffler is installed. A minimum insertion loss of 25 dB(A) is mandated for DG sets with capacities up to 1000 kVA in India.

This means that the exhaust muffler should reduce the noise level by at least 25 dB(A) compared to the original sound levels emitted directly by the generator. This level of insertion loss is essential for minimizing the environmental impact of diesel generator noise and ensuring compliance with regulatory standards.

We’ve helped 1,000+ industries stay stack-compliant. Here’s the checklist they trust most

Why Is DG Insertion Loss Testing Important?

As per CPCB norms, industrial noise levels must not exceed 75 dB(A) during the day and 70 dB(A) at night at the plant boundary.

However, even if DG set noise seems low, poor-quality silencers or acoustic enclosures can drastically affect overall compliance. That’s why insertion loss testing is conducted—to confirm whether the noise-reducing components are actually effective.

We help clients assess:

  • Silencer efficiency across frequency bands
  • Acoustic enclosure quality
  • Pre- and post-installation performance
  • Insertion loss value in dB(A) at key frequency points

Insertion Loss in DG Set

Insertion loss in a DG set refers to the reduction of sound levels achieved through noise control mechanisms like mufflers and acoustic enclosures. Diesel generator (DG) sets produce high noise levels, which can exceed permissible limits if not properly controlled. The insertion loss in a DG set is an important factor in meeting regulatory standards and ensuring minimal disturbance to the environment.

Read more about CPCB Guidelines for Stack Monitoring

2. Importance of Insertion Loss in Diesel Generators

Diesel generators are notoriously noisy machines. Without proper noise control measures, they can emit sound levels well above 85 dB(A), which is loud enough to cause discomfort and even potential hearing damage with prolonged exposure. Noise pollution from DG sets can disrupt nearby residential and commercial areas, leading to complaints and non-compliance with environmental regulations.

DG Set Noise Level

The noise level of a DG set varies based on factors such as engine size, fuel type, and operational conditions. Typically, a diesel generator without noise control measures can emit sound levels above 85 dB(A), which is hazardous to human health. Implementing proper noise reduction strategies, including mufflers and enclosures, helps in maintaining acceptable noise levels and avoiding regulatory violations.

CPCB Noise Standards for DG Sets

The Central Pollution Control Board (CPCB) mandates strict noise emission standards for diesel generator sets to reduce environmental noise pollution. For DG sets up to 1000 kVA, the maximum allowable noise level is 75 dB(A) measured at 1 meter from the enclosure surface. Additionally, the noise at the plant boundary must not exceed limits based on zone classification — for example, 70 dB(A) in industrial areas at night and 55 dB(A) in residential zones.

Every DG set must come with a certified acoustic enclosure capable of reducing noise by at least 25 dB(A), and users must maintain this insertion loss over time through proper upkeep.

These standards stem from GSR 371(E) notification dated 17th May 2002, which provides the legal foundation for noise regulation in DG operations.

Benefits of Proper Insertion Loss:

  • Noise Reduction: A minimum insertion loss of 25 dB(A) effectively lowers the generator’s noise to acceptable levels, reducing its impact on the surrounding environment.
  • Regulatory Compliance: By meeting the minimum required insertion loss, industries and businesses ensure compliance with national and local noise control regulations, avoiding penalties or fines.
  • Health and Safety: Reducing noise exposure helps protect the health of workers and residents in the vicinity of the generator. Prolonged exposure to high noise levels can lead to hearing loss, increased stress, and other health issues.

This article simplifies compliance through real-world monitoring examples that most EHS professionals will relate to.

3. Acoustic Enclosures for Diesel Generators

An acoustic enclosure is a soundproofing mechanism that encapsulates the diesel generator to reduce the noise it produces. These enclosures are designed to reduce the noise not only from the exhaust but also from the engine body and vibration. According to Indian standards, all manufacturers of DG sets with capacities of up to 1000 kVA must provide a standard acoustic enclosure with a minimum insertion loss of 25 dB(A).

Learn More about Stack Monitoring Kit

Features of a Good Acoustic Enclosure:

  • Material: Acoustic enclosures are typically made from sound-absorbing materials such as steel, which are lined with noise-dampening insulation.
  • Vibration Dampening: The enclosures often have vibration-isolating mounts that reduce noise caused by the generator’s vibrations.
  • Cooling and Ventilation: While reducing noise, an enclosure must also allow for proper air circulation to ensure the generator does not overheat during operation.

Importance of Acoustic Enclosures:

  • Compliance: Providing an acoustic enclosure with the required insertion loss helps manufacturers and users comply with the regulatory guidelines set by pollution control boards.
  • Noise Control: By limiting noise emissions, acoustic enclosures help minimize the disturbance to surrounding areas.
  • Durability: A good-quality acoustic enclosure ensures the longevity of the DG set by protecting it from environmental factors such as dust and moisture.
dg muffler perfect pollucon services
Diesel Generator DG muffler – Perfect Pollucon Services

4. Noise Levels and Control Measures

Even with a muffler and acoustic enclosure, it is crucial to take additional measures to control noise from diesel generators. These measures help ensure that noise levels outside the premises of the generator installation remain within acceptable limits.

Noise Control Strategies:

  • Proper Siting: The location of the DG set plays a significant role in noise control. DG sets should be placed as far away as possible from noise-sensitive areas, such as residential neighborhoods, hospitals, and schools. Natural barriers such as trees and walls can also help reduce the spread of noise.
  • Acoustic Barriers: If the DG set cannot be moved to a quieter location, consider installing acoustic barriers around the generator. These barriers can further reduce the transmission of sound waves to the environment.
  • Maintenance: Regular maintenance of the DG set, especially the muffler and acoustic enclosure, is essential to ensure optimal noise reduction performance.

DG Noise Monitoring

DG noise monitoring is essential for ensuring that diesel generators comply with noise pollution norms. Monitoring involves the use of sound level meters or real-time monitoring systems to measure noise emissions at different operational stages. Regular noise monitoring helps in identifying any deviations from permissible limits and implementing corrective measures to maintain compliance.

Read more about Stack Emission Monitoring Testing

5. Installation Guidelines for DG Sets

Proper installation of diesel generators is crucial for achieving the desired insertion loss and ensuring the efficient operation of the generator. Installation should be in strict compliance with the manufacturer’s recommendations, considering aspects like positioning, vibration control, and ventilation.

Key Installation Considerations:

  • Location: The DG set should be installed in a well-ventilated area to prevent overheating and ensure the smooth operation of the exhaust system. It should also be located away from noise-sensitive areas.
  • Foundation: The generator should be installed on a solid, stable foundation that minimizes vibration. Vibration can not only increase noise levels but also cause damage to the generator over time.
  • Acoustic Treatment: If a standalone acoustic enclosure is not possible, the generator room should be acoustically treated with soundproofing materials to ensure noise levels remain within permissible limits.

6. Maintenance of DG Sets

Routine maintenance is vital to maintaining the noise-reducing capabilities of diesel generators. Over time, wear and tear on the muffler, engine, and acoustic enclosure can lead to increased noise emissions if not properly maintained.

Maintenance Checklist:

  • Exhaust System: Inspect the exhaust system regularly for leaks, cracks, or damage. Replace worn-out parts to maintain optimal insertion loss.
  • Muffler Cleaning: The muffler should be cleaned periodically to prevent blockages that can reduce its effectiveness in controlling noise.
  • Enclosure Inspection: Check the acoustic enclosure for any damage or wear that may reduce its noise-reducing capabilities. Make necessary repairs or replacements to ensure continued performance.
  • Engine Maintenance: Ensure that the engine is running smoothly, as engine issues can lead to increased noise and vibration.

7. Certification and Compliance

Manufacturers, importers, and assemblers of diesel generators in India are required to have valid certifications of Type Approval and Conformity of Production. These certifications confirm that the DG sets meet the required environmental and safety standards, including noise emission limits.

Type Approval:

This certification ensures that the DG set design meets the required noise control standards, including the insertion loss requirement of 25 dB(A).

Conformity of Production:

This certification guarantees that all DG sets produced, imported, or sold conform to the approved design and meet the same performance criteria.

By ensuring that DG sets have these certifications, manufacturers and users can be confident that their generators comply with the regulatory noise emission standards and that they won’t face penalties for non-compliance.

CPCB Norms for DG Sets Above 1000 kVA

While most CPCB noise compliance rules apply to DG sets up to 1000 kVA, larger generators above 1000 kVA fall under additional scrutiny.

For these higher-capacity units:

  • Noise control is assessed case-by-case, based on load, design, and proximity to sensitive zones.
  • Insertion loss guidelines remain relevant, but CPCB may require custom acoustic validation.
  • Manufacturers often need to submit independent acoustic testing reports from NABL-accredited labs.

At Perfect Pollucon Services, we’ve assisted multiple industries in certifying high-capacity DG sets through custom acoustic design audits, boundary noise mapping, and real-time insertion loss analysis.

8. Acoustic Treatment for Generator Rooms

If it is not possible to install individual acoustic enclosures for each DG set, the generator room itself can be acoustically treated to reduce noise emissions. This involves adding soundproofing materials to the walls, floors, and ceilings of the room where the DG set is housed.

Acoustic Treatment Options:

  • Sound-Absorbing Panels: Installing sound-absorbing panels on the walls can reduce the amount of noise that escapes from the room.
  • Insulation: The walls of the generator room can be insulated with sound-dampening materials to block noise transmission.
  • Double Glazing: Windows in the generator room can be fitted with double-glazed glass to minimize the noise that escapes through them.

Acoustic treatment is particularly useful for large industrial facilities where multiple generators are installed in the same location, as it helps reduce overall noise pollution.

DG Insertion Loss Formula

Insertion loss (IL) in distributed generation (DG) systems refers to the reduction in power level or signal strength as energy passes through a component or network. The insertion loss formula is expressed as:

IL (dB) = 10 log(Pin / Pout)

where PinP_{in}Pin​ is the input power and PoutP_{out}Pout​ is the output power. The formula measures the loss in decibels (dB) and helps quantify the efficiency and performance of the component within the system. An increase in insertion loss indicates higher energy dissipation, which may result from factors such as impedance mismatches, resistance, or parasitic elements. Understanding and minimizing insertion loss is crucial for optimizing power delivery and system performance in DG setups.

Conclusion

The requirement for a minimum insertion loss of 25 dB(A) in diesel generators plays a critical role in reducing noise pollution and ensuring compliance with environmental regulations. By installing acoustic enclosures, properly siting the generator, maintaining the exhaust system, and adhering to manufacturer guidelines, industries and businesses can significantly reduce the noise impact of their DG sets. Regular maintenance and adherence to certification standards further ensure that DG sets continue to operate efficiently and quietly throughout their lifespan.

DG Backup Meaning

DG backup refers to the use of diesel generators as an alternative power source during electrical outages. Industries, commercial buildings, and residential complexes rely on DG backup to ensure continuous power supply. Noise control measures like insertion loss techniques help in minimizing the impact of DG backup systems on surrounding environments.

Real-World Application

Case Study:
A client in Ambernath faced repeated non-compliance due to high DG set noise. Our team conducted an insertion loss audit which revealed the silencer was offering just 8 dB(A) loss instead of the required 15+. Based on our report, they upgraded their silencer and passed the CPCB test within 10 days—saving lakhs in potential penalties.

Want to test your entire DG set for CPCB compliance?
Read our full guide on DG Set Noise Testing here

Source1

Source2

Source3

What is a good insertion loss?

A good insertion loss typically ranges from 20 to 30 dB(A) for industrial applications, including diesel generators. In India, a minimum insertion loss of 25 dB(A) is required for DG sets up to 1000 kVA to ensure adequate noise reduction.

How do you check for insertion loss?

To check for insertion loss, you measure the sound levels at two points: before and after installing the sound barrier, such as a muffler or acoustic enclosure. First, use a sound level meter to measure the noise directly from the source (e.g., diesel generator) without the muffler. Then, after installing the muffler, take a second reading at the same location. The insertion loss is the difference between the two sound levels, typically measured in decibels (dB).

What is insertion loss in a generator?

Insertion loss in a generator refers to the reduction in sound or signal level when a noise-reducing device, like a muffler or acoustic enclosure, is added. It represents the difference between sound levels before and after installation.

How is insertion loss measured in a diesel generator?

Insertion loss is measured by using a sound level meter to record noise levels before and after installing the muffler or acoustic barrier. The difference between these measurements, usually in decibels (dB), is the insertion loss.

What is a good insertion loss for a generator muffler?

A good insertion loss for a generator muffler is typically 25-30 dB(A). For DG sets up to 1000 kVA in India, a minimum insertion loss of 25 dB(A) is required by regulations.

What factors affect insertion loss in diesel generators?

Factors that affect insertion loss include the design and quality of the muffler, the acoustic properties of the enclosure, the frequency of the sound, and the placement of the noise-reducing components.

Why is insertion loss important for diesel generators?

Insertion loss is important because it helps reduce noise pollution from diesel generators, ensuring compliance with environmental regulations and creating a safer, quieter operating environment.

Can insertion loss vary over time?

Yes, insertion loss can vary due to factors like wear and tear of the muffler, accumulation of dirt or debris, or changes in operating conditions, which can reduce its effectiveness over time. Regular maintenance is needed to ensure optimal performance.

What is a good insertion loss value for DG sets?

It depends on the make and model, but generally, a loss of 15–25 dB(A) across the critical frequency range is expected.

Is insertion loss testing mandatory for CPCB compliance?

While not explicitly mandatory, poor insertion loss can cause total DG noise to exceed norms, leading to show cause notices or operational restrictions.

How is insertion loss measured?

We use calibrated sound meters to measure noise with and without the silencer under controlled conditions.

What is the noise monitoring for DG set?

Noise monitoring for DG sets involves measuring sound levels generated by diesel generators to ensure they remain within permissible limits prescribed by the CPCB (Central Pollution Control Board). At PPS, we conduct DG set noise compliance testing at the source (near the DG enclosure) and at the property boundary to check whether both levels meet legal standards. This helps industries and commercial premises avoid non-compliance notices and protects workers and nearby residents from harmful noise exposure.

What is the standard DG noise?

As per CPCB regulations:
The permissible DG set noise level is 75 dB(A) measured at 1 meter from the enclosure surface.
Additionally, noise at the property boundary must not exceed the applicable zone limits (e.g., 55 dB in residential areas at night).
Perfect Pollucon Services ensures that all readings are taken using calibrated sound level meters, following CPCB-approved procedures. We also help document noise levels for audit and compliance reports.

How to reduce DG noise?

At Perfect Pollucon Services, we recommend a combination of the following proven methods:
✅ Acoustic Enclosures: Installing CPCB-certified enclosures around DG sets significantly cuts noise.
✅ Proper Maintenance: Poorly maintained engines produce higher noise — regular servicing helps.
✅ Anti-vibration Mounts: These reduce structure-borne noise.
✅ Exhaust Mufflers or Silencers: Reduce noise from DG exhaust outlets.
✅ Relocation: Placing DG sets away from occupied areas or boundary walls when possible.
We offer noise audits and can suggest custom mitigation plans based on your DG setup.

What is the acceptable noise level for a generator?

For stationary diesel generators, the CPCB mandates a maximum of 75 dB(A) at 1 meter distance from the generator in open field conditions. However, acceptable levels may vary based on:
Local zonal classification (Industrial, Commercial, Residential, Silent)
Time of day (stricter at night)
Whether the generator is used indoors or outdoors
At Perfect Pollucon Services, we help clients ensure that their DG operations remain compliant 24×7, using certified equipment, trained professionals, and timely reporting.

Need help with DG Insertion Loss Testing?
With 25+ years in environmental monitoring, Perfect Pollucon Services offers certified DG set noise audits, expert reports, and actionable recommendations.

Contact us now or call +91 7045 651 859 to schedule your test.

Related Posts:

  • Ambient and in-plant workzone noise level monitoring by Perfect Pollucon Services V1
    Noise Level Monitoring & Testing
  • dg set and boiler stack height as per cpcb guidelines - Perfect Pollucon Services
    DG Set Stack Height As Per CPCB
  • ventilaton survey or air change survey by Perfect Pollucon Services
    Ventilation Survey
  • Lux & Illuminance Calculators by Perfect Pollucon Services
    Lux & Illuminance Calculators
  • Corrosion Control at data Centre & Indoor Air Quality Testing & Monitoring - Perfect Pollucon Services
    Corrosion Control at Data Center Explained
  • The Role of Calibrated Equipment in Accurate Stack Monitoring - Perfect Pollucon Services
    The Role of Calibrated Equipment in Accurate Stack…
  • noise monitoring guidelines by cpcb - perfect pollucon services
    Noise Monitoring Guidelines CPCB
  • Noise Level Measurement Procedure
    Noise Level Measurement Procedure
  • Stack Emission
    Stack Emission Monitoring & Testing
  • Ambient Air Sampling - Grab sample - Perfect Pollucon Services
    Ambient Air Sampling Methods
  • environmental monitoring at data centres by Perfect Pollucon Services
    Environmental Monitoring in Data Centers
  • noise mapping - perfect pollucon services
    Noise Mapping

Post navigation

10 Most Read Environmental Books
Ambient Air Monitoring Parameters: Ensuring Clean and Healthy Air

0 / 180

Environmental Monitoring Services

  • Ambient Air Quality Monitoring & Testing
  • Indoor Air Quality Monitoring & Testing
  • Air Quality Monitoring & Testing
  • Fugitive Emission Monitoring & Testing
  • Stack Emission Monitoring & Testing
  • Food Testing Laboratory Services
  • Noise Level Monitoring & Testing
  • Corrosion Testing Services
  • Ventilation Survey
  • Illumination Survey

Search

Download Our Brochure (682 kb)

Download Our Company Brochure

WhatsApp Chat with Perfect Pollucon Expert

Recent Posts

  • How Environmental Monitoring Helps Businesses Stay Compliant
  • Environmental Monitoring Jobs & Career Opportunities in India
  • Corrosion Coupon Testing: The Definitive Guide for Industries
  • Best Air Purifiers for Home in India (2025) – Expert Picks
  • AQI Display Boards Mandatory for Mumbai Sites
  • Hazardous Waste Management: A Guide from the Field
  • Types of Hazardous Waste
  • Form IV Hazardous Waste Return: Full Step-by-Step Filing Guide
  • How to Fill Form V – Environmental Statement Guide
  • Stack Emission Monitoring Checklist

Environmental Consultancy Services

  • Environmental Monitoring and Assessment
  • Environmental Impact Assessment
  • Effluent Treatment Plant
  • Effluent Treatment Plant Design
  • Consent to Establish, Consent to Operate and Renewal
  • Self Audit Report MPCB
  • Ventilation Survey
  • Tools
  • HTML Sitemap

Environmental Consultancy Services

  • Environmental Monitoring and Assessment
  • Environmental Impact Assessment
  • Effluent Treatment Plant
  • Effluent Treatment Plant Design
  • Consent to Establish, Consent to Operate and Renewal
  • Self Audit Report MPCB
  • Ventilation Survey
  • Tools
  • HTML Sitemap

Environmental Monitoring Services

  • Ambient Air Quality Monitoring & Testing
  • Indoor Air Quality Monitoring & Testing
  • Air Quality Monitoring & Testing
  • Fugitive Emission Monitoring & Testing
  • Stack Emission Monitoring & Testing
  • Food Testing Laboratory Services
  • Noise Level Monitoring & Testing
  • Corrosion Testing Services
  • Ventilation Survey
  • Illumination Survey

About Us

  • Home
  • Blog
  • About Us
  • Case Studies
  • Industries We Serve
  • Write for Us | Guest Posting
  • Privacy Policy
  • Terms and Conditions
  • Save our Contact By Scanning below Image
    • VCard of Perfect Pollucon Services

Registered Office

Perfect Pollucon Services – Environmental Consultancy Company

3 Krishna Koyna B, Majiwada Thane,
Maharashtra, India
400601

Email: [email protected]

Phone :

+91 9137 039 315

+91 9930 180 059

+91 7045 651 859

  • Privacy Policy
  • Terms and Conditions
  • Contact Our Experts
  • Sitemap
@Copyright Perfect Pollucon Services
DG Insertion Loss Testing for DG Sets – CPCB Noise Compliance