Skip to content
Skip to content
Welcome to Perfect Pollucon LLP Office Hours: 10:00am-7:00pm
Perfect Pollucon Services - Environmental Consultancy and Environmental Monitoring Services

Perfect Pollucon LLP

Environmental Consultant & Laboratory

Call Us 9967436537
Mail Us [email protected]
Maharashtra, India 3 Krishna Koyna B, Majiwada, Thane W
  • Home
  • Monitoring Services
    • Ambient Air Quality Monitoring & Testing Services
    • Indoor Air Quality Testing & Monitoring Services
    • Air Quality Monitoring & Testing Services
    • Airborne Particle Count Testing
    • Stack Emission Monitoring & Testing Services
    • Noise Level Monitoring & Testing Services
    • Food Testing Laboratory Services
    • Fugitive Emission Monitoring & Testing
    • Soil Testing & Investigation Laboratory
    • Drinking Water Quality Testing & Analysis Laboratory
    • Data Centre Corrosion Testing Services
    • Illumination Survey / Lux Monitoring
    • Airflow, Ventilation & ACH Testing Services
    • Noise Dosimetry Testing
  • Consultancy Services
    • Temperature and Relative Humidity Testing
    • Heat Stress & WBGT Assessment Services
    • Differential Pressure Testing & Cleanroom Pressure Mapping
    • Compressed Air Leak Detection & Ultrasonic Leak Survey
    • Electrical Thermography & Thermal Imaging Survey
    • Environmental Impact Assessment
    • Environmental Statement Form V
    • MPCB Consent to Establish, Operate and Renewal
    • Operation and maintenance of Effluent Treatment Plant
    • Effluent Treatment Plant Design
    • Six Monthly EC Compliance Report Service
    • Self Audit Report MPCB
    • Environmental Compliance
  • Industries
    • Pharmaceutical Industries
    • Chemical and Petrochemical Industry
    • Construction & Real Estate
    • Oil and Gas Or Petroleum Industry
    • Manufacturing / Production Industry
    • Corrosion Control at Data Center / IT Industry
    • Mining and Mineral Extraction
    • Food & Cold Storage Industry
    • Supply Chain & Warehouses
    • Data Centres
    • Railways & Metro Projects
    • Hospitality & Tourism
    • Retail and Shopping Malls
  • Blog
  • Tools
    • Air Monitoring Calculators
    • Stack Monitoring Calculators
    • Noise Monitoring Calculators
    • Carbon & Energy Footprint Calculators
    • Lux & Illuminance Calculators
    • ETP & STP Calculators for Form-V
    • ETP Design Calculators
  • About Us
    • Vision
    • Why We Built EHSSaral?
    • Our Work and Clients
    • Case Studies
    • Testimonials & Leave Us a Review
    • Trusted Partners
    • Careers
    • Guest Posting – Write for Us
    • Press Release
    • Our Features
  • Contact Us
REQUEST A QUOTE

Corrosion Testing Services for Data Centres, Server Rooms & IT Facilities

Assess airborne corrosion risk to sensitive electronic equipment with Perfect Pollucon LLP.

Perfect Pollucon LLP provides data centre corrosion testing services for server rooms and IT facilities. We help facility managers, IT infrastructure teams and consultants assess atmospheric corrosion risk around sensitive electronic equipment, interpret the findings and identify where further investigation or corrective action is needed.

Our environmental monitoring practice dates back to 2007, under Perfect Pollucon Services. We have served clients in the data centre and IT sector, while maintaining confidentiality around their identities and project details.

Our corrosion assessment scope is agreed before installation and identifies the copper and silver coupons, monitoring locations, exposure duration, laboratory analysis, reporting criteria and deliverables. The quotation also specifies arrangements for installation, retrieval and reporting, together with any additional environmental measurements.

Request a corrosion testing quotation | Call +91 9967436537

Based in Thane, we handle enquiries for facilities in Mumbai, Navi Mumbai, Thane, Pune and other serviceable locations. Share your site location, number of rooms and testing objective so we can confirm the assessment scope and quotation.

What Is Data Centre Corrosion Testing?

Data centre corrosion testing assesses how aggressively the local atmosphere reacts with metals relevant to electronic equipment.

In a typical passive assessment, prepared copper and silver coupons are exposed at selected locations. After the specified period, they are retrieved and analysed to evaluate corrosion film formation. The results support an assessment of atmospheric corrosivity for those locations and that exposure period.

This helps facility teams assess whether the air reaching their IT equipment is sufficiently controlled against corrosion risk.

A coupon assessment measures environmental exposure. It does not directly test every server, prove why a particular circuit board failed or predict an exact equipment failure date.

Why Test a Room That Looks Clean and Has Air Conditioning?

Visible cleanliness and comfortable room conditions do not establish that an environment is suitable for sensitive electronics.

Different assessments answer different questions:

AssessmentWhat it helps establish
Copper and silver corrosion couponsCorrosive effect of the atmosphere over the exposure period
Airborne particle countingNumber of airborne particles in specified size ranges
Temperature and humidity measurementsThermal and moisture conditions at monitored locations
Targeted gas measurementConcentration of the selected gas within the method’s capability
Airflow and pressure assessmentHow air moves and where contamination may enter

Passing one assessment does not automatically mean that the others will be satisfactory.

For example, a room can have low particle counts while still experiencing gaseous contamination. Conversely, a satisfactory corrosion result does not establish an ISO particle cleanliness class.

Where dust is also a concern, consider a separately defined airborne particle count testing service for server rooms and controlled environments.

When Should You Consider Corrosion Testing?

A corrosion assessment can support decisions when:

  • Commissioning a new data hall or server room.
  • Establishing baseline conditions before equipment deployment.
  • Investigating repeated component failures where environmental corrosion is suspected.
  • Reviewing an equipment manufacturer’s environmental requirements.
  • Checking conditions following HVAC, filtration or building modifications.
  • Assessing a facility exposed to nearby industrial emissions or other potential contaminant sources.
  • Comparing conditions before and after corrective work.
  • Planning periodic monitoring of critical IT environments.

Testing may also be relevant to network rooms, telecom equipment rooms and industrial control rooms containing sensitive electronics.

A hardware fault alone does not establish corrosion as the cause. Electrical, thermal, manufacturing and operational causes may require separate investigation.

Copper and Silver Corrosion Coupon Testing

Why Use Both Copper and Silver?

Copper and silver respond differently to atmospheric contaminants. A satisfactory result for one metal should not be used to assume that the other is also satisfactory.

Relevant equipment specifications commonly address both metals. For example, IBM’s environmental guidance on conductive contamination identifies separate copper and silver reactivity limits.

For a dual-metal assessment, request separate results for copper and silver at every monitoring location. Avoid accepting a single combined value that hides a higher result for one metal.

How Long Does Testing Take?

Passive coupon exposure commonly lasts approximately 30 days, followed by retrieval, laboratory analysis and report preparation.

The ASHRAE gaseous and particulate contamination guidelines describe month-long copper and silver coupon exposure for assessing data centre atmospheric corrosivity.

A one-day site visit is therefore different from completion of a month-long coupon study. The quotation should distinguish:

  1. Installation and site documentation.
  2. Exposure duration.
  3. Retrieval and transport.
  4. Laboratory turnaround.
  5. Final reporting.

If a shorter or different exposure period is proposed, establish the method, reporting basis and limitations before proceeding.

Does Testing Require Server Shutdown?

Passive coupons can generally be installed in an operating facility without shutting down servers. Placement remains subject to the facility’s access permissions, safety requirements and change-control process.

Coupons must be secured so they do not obstruct airflow, interfere with equipment or create a loose-object risk.

How a Corrosion Assessment Is Planned and Conducted

The final scope is agreed for the individual facility. A well-documented assessment follows the stages below.

1. Define the Assessment Objective

First establish whether the purpose is a baseline survey, an original equipment manufacturer’s requirement, a periodic review, a suspected contamination investigation or a check after corrective work.

Useful inputs include:

  • Room layout and number of separate data halls.
  • HVAC arrangements and outdoor-air pathways.
  • Equipment intake locations.
  • Previous corrosion or contamination reports.
  • Relevant manufacturer or customer specifications.
  • Planned changes during the monitoring period.

A clear objective helps avoid collecting results that cannot answer the client’s original question.

2. Select Representative Monitoring Locations

Coupon placement should relate to equipment exposure and the movement of air through the facility.

Potential locations include representative equipment intake areas, separate air-handling zones and locations selected to investigate suspected contaminant entry. A comparison location may be useful where the objective requires one.

The final location plan should explain what each position represents.

A single coupon in a convenient corner should not automatically be treated as representative of several floors or independently ventilated rooms.

Record each position using a location ID, room reference and installation details. Where photographs are restricted, use an approved sketch or location register.

3. Install and Document the Coupons

Use the selected coupon system’s handling and installation instructions. Exposed surfaces should not be touched, cleaned or otherwise altered.

Record the coupon identification, metal types, location, installation date and time, and relevant site conditions.

The facility team should know who to contact if a coupon is moved, damaged or disturbed.

4. Record Relevant Events During Exposure

Where available, retain temperature and humidity records and note changes that could affect interpretation, such as:

  • HVAC shutdowns or changes.
  • Filter replacement.
  • Construction or maintenance work.
  • Unusual door-opening activity.
  • A known contamination incident.
  • Changes in occupancy or facility operation.

These records provide context. They do not, by themselves, prove the source of an elevated result.

5. Retrieve and Analyse

Record the removal date and time and return the coupons using the laboratory or manufacturer’s specified packaging procedure.

The report should identify the analytical method and distinguish the measured result from any time-normalised value.

For atmospheric electronics assessments, corrosion film results must not be confused with pipeline coupon metal-loss measurements expressed in mm/year or mils per year.

Manufacturers such as Purafil describe corrosion classification coupons as a means of assessing the type and thickness of corrosion formed on the exposed surface.

6. Interpret Results and Identify Follow-Up

Review the results against the criteria agreed before testing.

The assessment should identify the affected locations, explain limitations and set out proportionate next steps. If corrective measures are introduced, follow-up testing can help evaluate conditions after the change.

Standards and Reference Criteria

ANSI/ISA-71.04

ANSI/ISA-71.04-2013 addresses airborne contaminants affecting process measurement and control systems.

Its environmental severity terminology includes G1, G2, G3 and GX. Where a classification is reported, the report should identify the standard edition, relevant criteria and basis for the classification.

A test report referring to ISA criteria is not a certification issued by ISA.

ASHRAE Guidance and Equipment Requirements

ASHRAE data centre guidance discusses copper and silver corrosion monitoring. Commonly referenced values are:

MetalCommonly referenced corrosion rate
CopperLess than 300 Å/month
SilverLess than 200 Å/month

An ångström, written Å, is a unit of length. 1 Å = 0.1 nanometre. These values describe corrosion film growth on the test surface, not a concentration of copper or silver in air.

The applicable equipment specification, guidance edition and agreed decision rule should govern the assessment. These reference values are not universal Indian statutory limits and do not provide a guarantee against equipment failure.

See ASHRAE’s guidance on data centres and telecommunication facilities for the relationship between contamination monitoring and environmental operating conditions.

Example: Copper Is Low but Silver Is Elevated

Illustrative example only. These are not Perfect Pollucon client results.

ParameterIllustrative resultReference used in this exampleInterpretation
Copper180 Å/monthLess than 300 Å/monthBelow the reference
Silver260 Å/monthLess than 200 Å/monthAbove the reference

The copper result does not cancel out the silver result. The elevated silver value warrants investigation under the agreed assessment criteria.

It would also be inappropriate to infer a precise gas concentration or predict a server failure date from these two figures alone.

What Should Your Corrosion Testing Report Contain?

A useful report needs to make each result traceable to the place and period it represents.

Report itemWhy it matters
Objective and agreed scopeDefines what the assessment covers
Coupon IDs and metal typesLinks results to individual samples
Location register or approved layoutShows where exposure occurred
Installation and retrieval detailsEstablishes actual exposure duration
Analytical method and reporting unitsExplains what was measured
Separate copper and silver resultsPrevents one result from masking the other
Criteria and referenced editionMakes the comparison reviewable
Site observations and exposure eventsProvides context for interpretation
Deviations and limitationsIdentifies constraints on the conclusion
RecommendationsConnects findings to practical next steps

When comparing quotations, confirm which of these deliverables are included. Also clarify who performs laboratory analysis and whether any claimed accreditation covers the specific method.

Corrosion Testing Report: Results and Interpretation

Anonymised 30-day copper and silver corrosion assessment showing the reported G2 classification, measured film thicknesses and interpretation notes Perfect PolluconDownload

To help facility managers understand what corrosion testing reveals, we have shared an anonymised summary of a completed copper and silver corrosion coupon assessment. Identifying details have been removed to protect confidentiality.

The report shows the results of a 30-day exposure, analysed using electrolytic reduction. The source report classified the tested environment as G2 – Moderate under ISA 71.04-2013.

What Did the Assessment Find?

Assessment parameterReported result
Exposure duration30 days
Analysis methodElectrolytic reduction
Total copper corrosion film thickness581 Å over 30 days
Total silver corrosion film thickness228 Å over 30 days
Overall environmental classificationG2 — Moderate

The copper corrosion film comprised 418 Å of copper oxide (Cu₂O) and 163 Å of unidentified corrosion products. The silver corrosion film comprised 228 Å of silver sulphide (Ag₂S).

These results describe corrosion film formation on the exposed coupons. They are not measurements of copper or silver concentrations in the air.

What Does G2 – Moderate Mean for a Facility?

The source report describes G2 as an environment where corrosion effects are measurable and may influence equipment reliability.

For a facility manager, this finding warrants a review of environmental conditions and the requirements of the installed equipment. It does not establish that every server is damaged, predict an imminent failure or identify the cause of a particular hardware fault.

Depending on the facility, follow-up may include reviewing contaminant entry pathways, humidity records, filtration performance and relevant equipment manufacturer specifications. Further testing can then be planned around the findings.

How Should the Projections and Gas Estimates Be Read?

The summary also includes one-year and five-year corrosion values. These are projections reproduced from the source report, not measurements collected over those periods. They should not be interpreted as guaranteed future corrosion levels or equipment service-life predictions.

Similarly, the hydrogen sulphide and sulphur dioxide ranges shown in the report are inferred estimates rather than direct gas measurements. Any decision requiring a confirmed gas concentration should use an appropriate measurement method.

What This Report Demonstrates

The example shows why a useful corrosion assessment should provide separate copper and silver results, a defined exposure period, an identified analysis method and a clear interpretation of environmental severity.

When discussing your assessment with Perfect Pollucon LLP, share any equipment manufacturer specifications or customer reporting requirements so the proposed scope can address them.

This document is an anonymised, reformatted summary of a source laboratory report. It is not the original signed laboratory report. Results relate to the assessed samples and exposure period and should not be applied to other locations or facilities.

What Happens If Corrosion Levels Are Elevated?

An elevated result should lead to a focused investigation. It does not establish that all equipment is damaged or identify a single source automatically.

Depending on the site, follow-up may include:

  • Reviewing outdoor-air intake positions and nearby activities.
  • Checking possible leakage or contaminant entry pathways.
  • Reviewing ventilation balance and pressure relationships.
  • Examining temperature and humidity trends.
  • Assessing existing gas-phase filtration and maintenance records.
  • Considering targeted contaminant measurements.
  • Involving the equipment manufacturer where damage is suspected.
  • Repeating the assessment after corrective work.

Ordinary particulate filtration and gas-phase filtration perform different functions. A dust filter should not be assumed to remove corrosive gases.

ASHRAE’s research on gaseous contamination and humidity examines how these factors interact in relation to corrosion and IT equipment reliability.

Changes to airflow, filtration or humidity settings should be reviewed by the responsible facility engineer against equipment and building requirements.

Where air movement needs investigation, ventilation surveys and airflow testing can be considered as a separate supporting scope.

How Often Should Corrosion Testing Be Repeated?

Set the frequency using the applicable equipment requirements, previous results, site risk and changes in operating conditions.

Useful review points include a baseline assessment, seasonal comparison where justified, and testing after a relevant incident or corrective measure.

ASHRAE’s 2023 handbook discussion links an expanded recommended humidity envelope to copper and silver monitoring at least twice a year. This is a specific operating-guidance context, not a blanket legal requirement that every Indian server room must test every six months.

A result describes the sampled locations during the exposure period. It should not be presented as proof that conditions will remain unchanged throughout the year.

Corrosion Testing Cost and Quotation

The cost depends on the agreed scope rather than floor area alone.

Main quotation factors include:

  • Number of monitoring locations and separate rooms.
  • Coupon system and metals included.
  • Exposure duration and monitoring cycles.
  • Installation and retrieval arrangements.
  • Laboratory analysis and reporting requirements.
  • Travel, access restrictions and site coordination.
  • Additional particle, airflow or environmental measurements.

For a useful quotation, share the site location, number of rooms or halls, purpose of testing, required completion date and any OEM or customer specification.

Compare complete study costs. A coupon-only price may exclude installation, retrieval, laboratory analysis, transport or interpretation.

Send your corrosion testing requirement to Perfect Pollucon LLP.

Why Choose Perfect Pollucon LLP?

Environmental Monitoring Experience Since 2007

Our environmental monitoring practice began as Perfect Pollucon Services in 2007. This background supports consideration of corrosion testing within the wider context of air quality and facility conditions.

Learn more about Perfect Pollucon LLP.

Experience Serving Data Centre and IT Clients

We have served multiple clients in this sector. We respect client confidentiality and do not publish identifiable project information without permission.

During scoping, discuss the reporting and confidentiality requirements relevant to your facility.

Access to Related Environmental Assessments

Corrosion risk may need to be reviewed alongside particle levels or airflow conditions. Relevant additional assessments can be scoped separately so the purpose and deliverables of each test remain clear.

Depending on the assessment objective, supporting services may include:

  • Airborne particle count testing.
  • Ventilation surveys and airflow testing.
  • Indoor air quality monitoring and testing.

These assessments address different aspects of the environment and should be selected according to the facility’s actual requirements.

Site-Specific Service Planning

Contact our Thane-based team for requirements in Mumbai, Navi Mumbai, Thane, Pune and other locations. We confirm site serviceability, access arrangements and the assessment scope before scheduling.

Request Corrosion Testing for Your Facility

Share a short description of your data centre, server room or IT facility and what you need the assessment to establish.

Useful information includes the site location, number of separate rooms, previous findings, applicable specification and preferred installation dates.

Perfect Pollucon LLP
Phone: +91 9967436537

Contact our team for a site-specific corrosion testing quotation.

Frequently Asked Questions

Is Data Centre Corrosion Testing the Same as Salt Spray Testing?

No. Atmospheric coupon testing assesses the corrosivity of the air at the monitored site. Salt spray testing exposes material or coating specimens to controlled laboratory conditions. A salt spray result does not establish the atmospheric corrosion class of an operating server room.

What Is G1 Corrosion Testing?

The expression usually refers to assessing whether the monitored environment meets the relevant G1 criteria. Ask for the actual copper and silver results, reference standard and exposure details rather than relying only on a “G1” label.

Is Corrosion Testing the Same as Indoor Air Quality Testing?

No. General indoor air quality testing and atmospheric corrosion assessment have different objectives. A general IAQ report should not be treated as evidence of low corrosion risk unless the necessary corrosivity assessment is included.

Can a Particle Counter Detect Corrosive Gases?

A standard optical particle counter counts particles within specified size ranges. It does not measure gas concentrations or replace copper and silver corrosion coupon testing.

Can the Test Identify the Exact Gas Causing Corrosion?

Some analytical results can support investigation of likely contaminant types. A precise gas concentration or source attribution requires an appropriate method and supporting evidence. It should not be assumed from a coupon severity label alone.

Can One Coupon Represent an Entire Data Centre?

Not automatically. Separate rooms, airflow zones and exposure pathways may require separate monitoring locations. The sampling plan should match the question being investigated.

Does a Satisfactory Report Guarantee That Servers Will Not Fail?

No. It documents the assessed environmental conditions within the scope and limitations of the study. Hardware can fail for reasons unrelated to corrosion, and site conditions may change later.

Is Corrosion Testing Mandatory for Every Indian Data Centre?

Do not assume a universal requirement. Review the facility’s applicable contractual, OEM, customer and certification requirements, and any specific legal obligation. Technical guidance should not be presented as legislation.

Do You Disclose Client Names or Data Centre Layouts?

Client identities and identifiable project details are kept confidential. Any proposed use of a report extract, photograph or project description requires appropriate permission and removal of sensitive information.

Technical References

  • ISA: ANSI/ISA-71.04-2013 — Environmental Conditions for Process Measurement and Control Systems: Airborne Contaminants.
  • ASHRAE Handbook: Data Centers and Telecommunication Facilities.
  • ASHRAE Research: Controlling Data Centers’ Air Pollution.
  • ASHRAE: 2011 Gaseous and Particulate Contamination Guidelines for Data Centers.
  • IBM: Conductive Contamination.
  • Purafil: Corrosion Classification Coupons.

Environmental Monitoring Services

  • Ambient Air Quality Monitoring & Testing Services
  • Indoor Air Quality Testing & Monitoring Services
  • Air Quality Monitoring & Testing Services
  • Airborne Particle Count Testing Service for Cleanrooms, Server Rooms and Controlled Areas
  • Stack Emission Monitoring & Testing Services
  • Noise Level Monitoring & Testing Services
  • Data Centre Corrosion Testing Services
  • Airflow, Ventilation & ACH Testing Services
  • Personal Noise Dosimetry Testing Services for Industries
  • Illumination Survey
  • Electrical Thermography & Thermal Imaging Survey Services in Mumbai, Thane & Navi Mumbai
  • Compressed Air Leak Detection & Ultrasonic Leak Survey Services
  • Differential Pressure Testing & Cleanroom Pressure Mapping Services
  • Heat Stress & WBGT Assessment Services
  • Temperature and Humidity Testing Services in Mumbai, Thane & Navi Mumbai

Search

Download Our Brochure (682 kb)

Download Our Company Brochure

WhatsApp Chat with Perfect Pollucon Expert

Recent Posts

  • Compressed Air Leak Detection Guide for Industrial Plants
  • Compressed Air Leak Cost Calculator & Industrial Leakage Guide
  • Noise Dosimetry vs Area Noise Monitoring: Factory Guide
  • Noise Dosimetry Report: Dose, TWA, Leq & Peak Explained
  • Noise Dosimetry Study Procedure: Factory Preparation
  • Ai Agents Need A Compliance Stop Rule Before Environmental Automation Scales
  • Ventilation & Airflow Testing in Factories: ACH & Air Velocity Guide
  • How Is Cleanroom Particle Count Testing Conducted? A Step-by-Step Field Guide
  • Cleanroom Particle Count Limits: ISO 14644-1 Guide
  • Top 15 Field Failures in Stack Monitoring & How to Prevent Them | Expert Guide

Environmental Consultancy Services

  • Environmental Monitoring and Assessment
  • Environmental Impact Assessment
  • Effluent Treatment Plant
  • Effluent Treatment Plant Design
  • Consent to Establish, Consent to Operate and Renewal
  • Six Monthly EC Compliance Report Service
  • Self Audit Report MPCB
  • Environmental Compliance in India
  • Airflow, Ventilation & ACH Testing Services
  • Tools
  • HTML Sitemap

Environmental Consultancy Services

  • Environmental Monitoring and Assessment
  • Environmental Impact Assessment
  • Effluent Treatment Plant
  • Effluent Treatment Plant Design
  • Consent to Establish, Consent to Operate and Renewal
  • Six Monthly EC Compliance Report Service
  • Self Audit Report MPCB
  • Environmental Compliance in India
  • Airflow, Ventilation & ACH Testing Services
  • Tools
  • HTML Sitemap

Environmental Monitoring Services

  • Ambient Air Quality Monitoring & Testing Services
  • Indoor Air Quality Testing & Monitoring Services
  • Air Quality Monitoring & Testing Services
  • Airborne Particle Count Testing Service for Cleanrooms, Server Rooms and Controlled Areas
  • Stack Emission Monitoring & Testing Services
  • Noise Level Monitoring & Testing Services
  • Data Centre Corrosion Testing Services
  • Airflow, Ventilation & ACH Testing Services
  • Personal Noise Dosimetry Testing Services for Industries
  • Illumination Survey
  • Electrical Thermography & Thermal Imaging Survey Services in Mumbai, Thane & Navi Mumbai
  • Compressed Air Leak Detection & Ultrasonic Leak Survey Services
  • Differential Pressure Testing & Cleanroom Pressure Mapping Services
  • Heat Stress & WBGT Assessment Services
  • Temperature and Humidity Testing Services in Mumbai, Thane & Navi Mumbai

About Us

  • Home
  • Blog
  • Our Vision & Mission
  • About Us
  • Case Studies
  • Industries We Serve
  • Write for Us | Guest Posting
  • Privacy Policy
  • Terms and Conditions
  • Explore our EnviroTech platform: EHSSaral.com

Registered Office

Perfect Pollucon LLP – Environmental Consultancy Company
3 Krishna Koyna B, Majiwada Thane,
Maharashtra, India
400601
Email: [email protected]
Phone :
+91 9930 180 059
+91 7045 651 859
Perfect Pollucon Services (proprietorship firm reg. 2009) is now Perfect Pollucon LLP (CIN : ACP-2349) (reg in Jun’2025)

  • Privacy Policy
  • Terms and Conditions
  • Contact Our Experts
  • Sitemap
@Copyright Perfect Pollucon LLP
Data Centre Corrosion Testing Services